摘要:

介绍了某数据中心项目水蓄冷系统设计内容,分析比较了采用闭式蓄冷罐、消防水池(兼冷却水补水池)、独立水池不间断供冷及日间释冷系统3种不间断供冷系统的利弊,以及采用闭式蓄冷罐和独立水池不间断供冷及日间释冷系统的运行费用。经技术和经济比较,不建议数据机房类项目将冷却水补水池或独立水池用于水蓄冷。

关键词:数据中心;水蓄冷;不间断供冷;闭式蓄冷罐;消防水池;运行费用

Abstract:

This paper presents the design content of the water cold storage system of a data center project, and analyses and compares the advantages and disadvantages of three kinds of uninterruptible cooling systems using closed cold storage tank, fire reservoir (cooling water make-up pool), independent pool uninterruptible cooling and daytime cooling release system, and the operating expense of the closed cold storage tank and independent pool uninterruptible cooling and daytime cooling release system. After technical and economic comparison, it is not recommended to use a cooling water make-up pool or independent pool for water cold storage in data room projects.

Keywords:data center; water cold storage; uninterruptible cooling; closed cold storage tank; fire reservoir; operating expense