办公楼空调冷热负荷的计算分析——关于北京地区办公楼外区冬季冷负荷的几点看法
Cooling and heating load calculation of air conditioning in office buildings—discussion on outer zone cooling load for Beijing office buildings in winter
摘要:
以北京银谷大厦办公楼为例,围绕着如何改进原建筑与空调系统方案,对其空调冷热负荷作了动态计算分析。给出了遮阳系数分别为0.6和0.3时内外区冬夏季的冷热负荷计算结果,发现外区冬季白天有冷负荷;遮阳系数减小节能效果明显。
关键词:办公楼,空调动态负荷计算,冬季,外区,冷负荷,遮阳系数
Abstract:
With the example of Beijing Yingu Building, aiming at improving original building and air conditioning scheme, calculates and analyses dynamic load of air conditioning. Provides cooling and heating load values in inner and outer zones in winter and summer when shading coefficient is separately 0.6 and 0.3. Finds that there is cooling load in outer zone in winter daytime and reducing shading coefficient has remarkable energy saving effect.
Keywords:office building, dynamic load calculation of air conditioning, winter, outer zone, cooling load, shading coefficient