某大中型综合性体育场馆冰蓄冷系统运行方案优化
Optimization of operation scheme of ice cool storage system in a large and medium-sized comprehensive gymnasium
摘要:
以杭州某大中型综合性体育场馆为例,探讨冰蓄冷空调系统运行策略的优化。研究了85%、75%、50%及25%负荷率下冰蓄冷系统的运行策略,并对比了传统冷水机组优先控制策略与优化运行策略的运行费用。结果表明,不同负荷率下的优化运行策略可实现“削峰填谷”效果,并分别节约20%、22%、27%与21%的日运行费用。验证了优化运行策略的可行性和有效性,为冰蓄冷系统在综合性体育场馆的应用提供了依据。
Abstract:
Taking a large and medium-sized comprehensive gymnasium in Hangzhou as an example, the optimization of the operation strategy of the ice cool storage air conditioning system is discussed. The operation strategies of the ice cool storage system under 85%, 75%, 50% and 25% load rates are studied, and the operating costs of the traditional chiller priority control strategy and optimal operation strategy are compared. The results show that the optimal operation strategy under different load rates can achieve the effect of “peak load shifting”, and save 20%, 22%, 27% and 21% of the daily operating costs, respectively. The feasibility and effectiveness of the optimized operation strategy are verified, which provides a basis for the application of the ice cool storage system to comprehensive gymnasium.
Keywords:gymnasium; ice cool storage system; control strategy optimization; load rate; peak load shifting; economic analysis

			