暖通空调>期刊目次>2011年>第9期

高等级生物安全实验室全新风直流空调系统热回收方案分析

Heat recovery scheme about all fresh air conditioning system for advanced biosafety laboratory

刘培源,李侃,李著萱
中国中元国际工程公司

摘要:

探讨了高等级生物安全实验室全新风直流空调系统的热回收方案,指出了显热回收的液体循环式热回收器最适合高等级生物安全实验室热回收方式。通过计算分析了我国部分主要城市的液体循环式热回收方案经济性,得到了节能效益随着纬度的升高而提高的结论,并给出了定量的分析结果。

关键词:生物安全实验室,液体循环式热回收器,经济性,节能

Abstract:

Discusses the heat recovery scheme, and points out that the liquid circulation heat recovery equipment is the most suitable heat recovery equipment for the advanced biosafety laboratory. Through calculating and analyzing the economic effects of liquid circulation heat recovery equipment for main cities in China, concludes that the quantity of energy saving is improved with the latitude increasing, and gives the quantitative analysis results.

Keywords:biosafety laboratory (BSL), liquid circulation heat recovery equipment, economic effect, energy efficiency
本站下载
镜像服务器下载