惠州某通信大楼空调系统节能改造

Air conditioning system energy efficiency reconstruction of a telecommunication building in Huizhou

闫军威,康英姿,周璇,高志明
华南理工大学

摘要:

分析了通信类建筑空调系统的能耗特点,针对惠州某通信大楼运行过程中存在的问题,提出了将多种空调节能技术与科学管理方法相结合的空调系统节能改造方案。现场实测数据显示,实施节能改造后,空调系统月平均节能率达32.2%,每年可减少电耗97.8万kWh,取得了良好的节能效果与经济效益。

关键词:通信建筑,空调系统,节能改造

Abstract:

Analyses the energy consumption characteristics of telecommunication buildings. Aiming at operating problems of the air conditioning system, proposes an air conditioning energy efficiency reconstruction scheme for the telecommunication building in Huizhou, Guangdong Province, in which are applied multiple energy saving technologies and scientific management methods. The field measured data demonstrates that the retrofit scheme has a good energy saving effect and economic benefit with monthly mean energy saving ratio up to 32.2% and 978 MWh power consumption saved per year.

Keywords:telecommunication building, air conditioning system, energy efficiency reconstruction