暖通空调>期刊目次>2021年>第1期

负压屏障环境动物生物安全实验室控制系统

Control system of negative pressure environment for animal biosafety laboratories

晋生【1】 吴建利【2】
【1】中国疾病预防控制中心 【2】铭基电子技术(北京)有限公司蒋

摘要:

通过分析负压控制房间的温度、湿度、洁净度、压力等参数,根据负反馈控制原理调节总送排风管道上变频器频率,根据房间高低态运行工况控制送风两态阀,以及根据房间压差控制排风变风量阀等组合式PID调节方法进行压差和定向流控制。搭建系统监控平台实现各房间负压控制要求,满足负压梯度和定向流及其他参数要求,有效避免交叉感染。

关键词:负压屏障环境,动物生物安全实验室,监控系统,负反馈,变风量阀

Abstract:

Through the analysis of the temperature, humidity, cleanliness, pressure and other parameters of a negative pressure control room, based on the negative feedback control principle, obtains the control of the pressure difference and directional flow by combined PID adjustment methods, including adjusting the converter frequency of  the general supply and exhaust pipes, controlling the two-state air supply valve by the high-low operating conditions of the room, and controlling the variable exhaust air volume valve according to the room pressure difference. Sets up a system monitoring platform to realize the negative pressure control requirements of each room, meet the negative pressure gradient, directional flow and other parameter requirements, and effectively avoid cross-infection.

Keywords:negative pressure environment, animal biosafety laboratory, monitoring system, negative feedback, variable air volume valve