某医院手术部洁净空调新风系统改造技术应用及分析
Application and analysis of outdoor air system transformation technology of clean air conditioning in operation departments of a hospital
摘要:
通过现场调研和测试诊断,分析了某医院手术部洁净空调新风系统存在的主要问题。采取相应的改造技术,包括新风机组检查清洗、冷水机组更换改造、新风机组深度除湿再热改造及设置配套新风控制系统等,有效解决了现有的问题,使各手术室的温湿度均满足了设计和标准要求,改造效果显著。
Abstract:
Through field investigation and test diagnosis, analyses the main problems of outdoor air systems of clean air conditioning in the operation departments of a hospital. Adopts the corresponding transformation technologies, including inspection and cleaning of outdoor air handling units, replacement and reconstruction of water chillers, deep dehumidification and reheating of outdoor air handling units, and installation of auxiliary outdoor air control systems, which effectively solves the existing problems and makes the temperature and humidity of each operating room meet the design and standard requirements, with a remarkable transformation effect.
Keywords:hospital operation department, outdoor air system, diagnostic analysis, transformation technology, deep dehumidification, transformation effect