某观众厅夏季座椅送风气流组织的模拟与测试分析
Simulation and test of air distribution in an auditorium using seat-air-supply in summer
摘要:
通过数值模拟与现场测试,分析了座椅送风条件下观众厅的气流组织与舒适性。指出剧场内采用座椅送风方式时应注意的问题,如送风道和静压箱应分区,池座和楼座前面几排无法使用静压箱送风,楼座温度比池座稍高等。
关键词:座椅送风,观众厅,气流组织,测试,模拟
Abstract:
Based on numerical simulation and site test, analyses the air distribution and comfort in the auditorium under the condition of seat-air-supply. Points out the problems for attention when using the seat-air-supply in theatre, such as air supply duct and air plenum chamber should be zoned, air plenum chamber cannot be used in a few rows in the front of loge and balcony for supplying air, and the temperature in balcony is slightly higher than that in loge.
Keywords:seat-air-supply, auditorium, air distribution, test, simulation