集中供热智能通断调节模式的节能效果分析
Analysis of energy saving performance for central heating systems under intelligent on-off regulation mode
摘要:
指出了集中供热系统质调节的局限性。针对不同连接形式的室内供暖系统,对智能通断调节技术的节能效果进行了模拟分析,结果表明,智能通断调节相比理想质调节方式,对于水平单管串联系统,可降低33%的能耗;对于垂直单管串联系统,可降低30%的能耗;对于高校学生公寓,寒假期间若实行低温调控,还可节能20%,节能效果明显。
关键词:集中供热,智能通断调节,节能,理想质调节
Abstract:
Puts forward the limitation of unified constant flow control for central heating system. Based on indoor heating systems with different connection modes, analyses the energy saving effect of intelligent on-off regulation by means of simulation method. The result shows that compared with ideal constant flow control, on-off regulation saves energy obviously and can reduce energy consumption by 33% in horizontal one-pipe series system, 30% in vertical one-pipe series system and 20% in college dormitories when low temperature control scheme is adopted in winter vacation.
Keywords:central heating, intelligent on-off regulation, energy saving, ideal constant flow control