暖通空调>期刊目次>2019年>第8期

降低血液病房顶部集中送风面积的样板间实验研究——国标《医院洁净护理与隔离单元技术标准》编制组系列探讨问题之三

Experimental research on reducing top concentrated air supply ceiling area in model hematology ward: Part 3 of the series of research practice of national standard Technical code on clean nursing and

马兆勇[1] 蒋国清[1] 许钟麟[2] 曹国庆[2] 潘红红[2] 王维平[3]
[1]苏州通快净化科技有限公司 [2]中国建筑科学研究院有限公司 [3]解放军总医院第五医学中心

摘要:

在面积9 m2、高2.5 m的血液病房样板间中进行了实验。在顶部送风尺寸每边比床边外延0.4 m的条件下,室内达到远低于3.5粒/L浓度的5级洁净度要求;床面0.4 m以上床头位置风速低于0.1 m/s,远低于避免吹风感的0.12 m/s要求;可比常规做法节能1/3~2/3。

关键词:血液病房,顶部集中送风,吹风感,高效过滤器,送风面积

Abstract:

 Performs an experiment in a model hematology ward with an area of 9 m2 and a height of 2.5 m. The results show that the cleanliness can be reached class-5 (indoor particle concentration much lower than 3.5 particles/L) when each side of top concentrated air supply ceiling is 0.4 m longer than the bedside. Meanwhile, the air velocity at 0.4 m height of bed head is lower than 0.1 m/s, which is far below blowing feeling velocity of 0.12 m/s. In addition, this air supply model can save 1/3 to 2/3 energy than regular project.

Keywords:hematology ward, top concentrated air supply, blowing feeling, high efficiency particulate air filter, air supply area