间接蓄冷直接供冷式水蓄冷系统
Indirect charging and direct discharging system of chilled water storage
摘要:
基于工程中常用的3种水蓄冷系统的优缺点分析,提出了间接蓄冷直接供冷式水蓄冷系统。详细介绍了该系统的工作原理和运行策略,并进行了经济性分析。结果表明:该系统流程简明,运行稳定、可靠,解决了原来水蓄冷系统中存在的主机效率低、开式系统泵耗大且可能存在压差大导致电动阀损坏等问题。
关键词:水蓄冷,间接蓄冷,运行策略
Abstract:
Based on the advantage and disadvantage analysis of commonly used three chilled water storage systems, presents the improved system. Describes in detail the working principle and operating strategies and performs the economic analysis. As a result, the system features simple flow process and stable and reliable operation, and can solve the problems existed in original system such as lower efficiency of refrigerating machines, extra energy consumption of pumps in open systems and electric valve damage resulting from possible over-large pressure difference.
Keywords:chilled water storage, indirect charging, operation strategy