冷却塔供冷技术用于数据中心的节能性分析
Energy saving analysis of cooling tower cooling technology in data centers
摘要:
针对数据中心的能耗特点,分析了冷却塔供冷技术的影响因素。通过建立模型,分析了各运行工况下的冷水系统综合性能系数WSCOP。根据北京、上海和广州地区的全年室外气象参数,分别计算了冷水系统全年运行能耗,分析了冷却塔供冷技术的运行时长及节能效果。
关键词:数据中心,冷却塔,免费供冷,冷水机组,性能系数,板式换热器
Abstract:
According to the energy consumption characteristics of data centers, analyses the influencing factors of cooling tower cooling technology. By establishing a model, analyses the comprehensive coefficient of performance of chilled water system (WSCOP) under various operating conditions. Based on the annual outdoor air design conditions in Beijing, Shanghai and Guangzhou, calculates the annual energy consumption of the chilled water system respectively, and analyses the operating time and energy saving effect of the cooling tower cooling technology.
Keywords:data center, cooling tower, free cooling, water chiller, coefficient of performance, plate heat exchanger