成都双流机场T1航站楼冬季室内参数实测与分析
Testing and analysis of indoor air conditioning parameters in winter for Chengdu Shuangliu Airport Terminal 1
摘要:
2010年冬季对该机场航站楼室内相关空调设计参数进行了测试,分析了温度、相对湿度及风速的测试结果。结果表明,冬季航站楼室内存在温度偏高、相对湿度偏低,大厅冷风侵入严重等问题。各参数分布特性可为航站楼气流组织的优化设计及空调系统控制提供参考。
关键词:空调参数,竖直分布,实测,分析,航站楼
Abstract:
Measures the related indoor air conditioning design conditions in the building in the winter of 2010. Analyses the test results of temperature, relative humidity and air velocity. The result shows that some problems, such as high temperature, low humidity and large air infiltration, exist in the terminal building. The gained parameter distribution characteristics can be uses as a reference for the optimization of air distribution and the control of air conditioning system for the terminal building.
Keywords:air conditioning parameter, vertical distribution, testing, analysis, terminal building