暖通空调>期刊目次>2018年>第11期

不同室外温度下复叠式空气源热泵蓄能除霜运行特性实验研究(2):蓄能除霜模式

Experimental study on energy storage and defrosting characteristics of cascade air-source heat pump at different outdoor temperatures(2): Energy storage defrosting mode

曲明璐[1] 唐雍博[1] 秦瑞丰[1] 余倩[2] 彭博[3]
[1]上海理工大学 [2]中国联合工程公司 [3]上海核工程研究设计院有限公司

摘要:

在2种不同室外温度工况下,实验研究了系统在开启蓄能除霜模式时的运行特性,分析了蓄热器的放热特性和高、低温级运行特性。结果表明:2种工况下,机组除霜时低温级的吸气压力均在0.236 MPa以上,系统除霜性能稳定,高温级的平均制热量能达到正常制热时的55.4%以上,说明蓄热器能够提供稳定的热源。

关键词:空气源热泵,复叠式循环,蓄热器,除霜,室外温度,低温级,高温级

Abstract:

Experimentally studies the characteristics of energy storage defrosting mode under two outdoor temperature conditions. Analyses the discharge performance of the thermal accumulator and the characteristics of the high and low temperature cycles. The results show that under the two conditions, the suction pressure of the low temperature cycle is higher than 0.236 MPa. The system defrosting performance is stable. The average heating capacity of the high temperature cycle is more than 55.4% of the normal heating capacity. The thermal accumulator can provide a stable heat source.

Keywords:air-sourceheatpump,cascadecycle,thermalaccumulator,defrosting,outdoortemperature,lowtemperaturecycle,hightemperaturecycle