蒸发冷却冷水机组在克拉玛依市文体中心集中制冷站中的应用
Application of evaporative cooling water chillers to central refrigeration station of Karamay Cultural and Sports Center
摘要:
克拉玛依市文体中心集中制冷站采用蒸发冷却冷水机组。阐述了该项目工程概况与温湿度独立控制空调系统,并与机械制冷的电耗作了对比。该项目综合制冷性能系数达到10.75,与同规模机械制冷相比,小时电耗减少了1 672 kW·h,年电耗减少了158.9万kW·h。总结了项目设计中的问题,为促进蒸发冷却空调在干燥地区的使用提供参考。
Abstract:
The evaporative cooling water chillers are applied to the project of Karamay Cultural and Sports Center. Elaborates the project profile and temperature and humidity independent processed air conditioning system, and compares its electricity consumption with the mechanical refrigeration. The comprehensive cooling performance coefficient is 10.75. Compared with the same cooling capacity of mechanical refrigeration, the hourly electricity consumption decreases by 1 672 kW·h, and the annual electricity consumption decreases by 1.589 million kW·h. Summarizes the design problems in this project, and provides the references for the evaporative cooling air conditioning system application in dry areas.
Keywords:evaporative cooling air conditioning, mechanical refrigeration, temperature and humidity independent processed air conditioning system, evaporative cooling water chiller, energy saving