我的订单 | 我的收藏 | 加入收藏 | 返回首页
暖通空调杂志社>期刊目次>2018年>第2期

定压差点的分布式变频改造技术应用

Application of distributed variable frequency technology based on fixed pressure control point

顾吉浩[1] 张 明[2] 齐承英[1] 杨 宾[1] 孙春华[1] 夏国强[1]
[1]河北工业大学 [2]国家电投集团河南电力公司

摘要:

在建立智慧热网平台的基础上,采用分布式变频技术对某供热系统进行了改造。选择节点22为定压差点,恒定其压头为15 m,解决了原有供热管网承压偏高和水力不平衡问题。2015—2016年供暖季的运行结果表明,各换热站的实际流量、耗热量与设计值均比较吻合,达到了预期效果。

关键词:分布式变频技术,定压差点,智慧热网,水力平衡,改造

Abstract:

Based on the establishment of a smart heat network platform, reforms a heat supply system by the distributed variable frequency technology. Chooses the node 22 as the fixed pressure point, and controls its pressure head at 15 m, solving the problems of high pressure and serious hydraulic imbalance in the original heating network. The operating data during the heating season of 2015-2016 shows that the actual flow rate and heat consumption are consistent with the design values, achieving the expected effect.

Keywords:distributedvariablefrequencytechnology,fixedpressurepoint,smartheatnetwork,hydraulicbalance,reform