暖通空调>期刊目次>2017年>第5期

贴附射流送风加热墙壁面效果试验研究

Experimental study on heating efficiency of wall surface using vertical wall-attached air jet

张 飞 魏 兵 胡 蔓 吴恩龙
华北电力大学

摘要:

针对地下室墙壁面易结露的问题,对贴附射流送风加热墙壁面的效果进行了试验研究,以达到防墙壁面结露的目的。结果表明,送风角度为0°、送风口距墙壁面的水平距离为5.0 cm时加热墙壁面效果较好。

关键词:贴附射流,送风角度,加热壁面,防结露,速度衰减

Abstract:

Aiming at the wall surface condensation in the basement, carries out an experimental research on the heating efficiency of the wall surface using vertical wall-attached air jet to prevent the condensation on the wall. The test results show that the better effect of wall heating is achieved when the air supply angle is 0° and the optimal value of horizontal distance between the wall and the air diffuser is 5.0 cm.

Keywords:wall-attachedairjet,supplyairangle,heatingwall,anti-condensation,velocityattenuation