数据中心冷水系统空调末端分析

Analysis on air conditioning terminal of chilled water system in data center

罗海亮,娄小军
中国移动通信集团设计院有限公司

摘要:

以冷水系统的空调末端为研究对象,根据布置位置、冷媒类型对空调末端进行了分类。结合实际工程,对列间级、机架级空调末端的装机率、空调末端PUEkm进行了计算,并进行了假负载测试,结果显示列间级、机架级空调末端的节能效果显著。

关键词:数据中心,空调末端,PUE,装机率,节能

Abstract:

Taking the air conditioning terminal of chilled water system as the study object, classifies the air conditioning terminal by location and the refrigerants. Combined with the engineering, calculates the unit proportion and PUE of the inter row and the rack terminals, and makes the different loads test. The results show that the above air conditioning terminals have significant energy saving effect.

Keywords:data center, air conditioning terminal, PUE, unit proportion, energy saving