摘要:

通过采用节能抑菌型空调器、超低阻新风过滤段、装配式围护结构等专利成果,验证了Ⅱ级洁净手术室换气次数降为24 h-1是可行的,实验结果表明节能方案和常规方案相比可节能50%

关键词:洁净手术室,换气次数,节能抑菌型空调器,超低阻新风过滤段,装配式围护结构

Abstract:

By adopting the patent results such as bacteriostatic type energy saving air conditioner, ultra low resistance fresh air filtration section and prefabricated envelope, verifies the feasibility of reducing the air change rate of class II clean operating room to be 24 h-1. The experimental results show that the energy saving scheme can save energy by 50% than conventional scheme.

Keywords:cleanoperatingroom,airchangerate,bacteriostatictypeenergysavingairconditioner,ultralowresistancefreshairfiltrationsection,prefabricatedenvelope