暖通空调>期刊目次>2016年>第4期

吊顶热管空调系统在某数据中心应用的探讨

Discussion on application of suspended ceiling heat pipe air conditioning system to a data center

邱成,秦艳,方大伟,钟建法
浙江盾安人工环境股份有限公司

摘要:

对某高热密度数据中心机房采用的吊顶热管空调系统进行了运行情况测试,结果表明,冷、热通道温度满足设计要求,能耗指标PUE优于设计值。指出了系统存在的不足,提出了优化设计方案,为绿色数据中心空调系统设计积累了实践经验。

关键词:数据中心,吊顶热管空调系统,冷热通道温度,电源使用效率,优化设计

Abstract:

Tests the operational condition of the suspended ceiling heat pipe air conditioning system applied to a high heat density data center. The results show that the temperature of cold and hot channel can meet the design requirements, and energy consumption indicator(PUE)is lower than the designed value. Points out the deficiencise of the system and gives out the optimal design scheme, accumulating practical experience for the air conditioning system design of green data center.

Keywords:datacenter,suspendedceilingheatpipeairconditioningsystem,temperatureofcoldandhotchannel,PUE,designoptimization