暖通空调>期刊目次>2013年>第7期

基于运行数据的冷凝器结垢故障检测与诊断研究

Condenser scaling fault detection and diagnosis based on operating data

赵云峰[1,2],胡孟娣[3],陈友明[1],陈永康[4],秦建英[4],周强[4]
[1]湖南大学,[2]中信建筑设计研究总院有限公司,[3]浙江科技学院,[4]太古地产管理有限公司

摘要:

提出了基于模型方法的离心式冷水机组故障检测与诊断策略,选取4个有典型物理意义的特性参数标示冷水机组的运行情况,运用机组正常运行时的数据建立了特性参数预测模型,通过比较每个特性参数的计算值和基准值得到了残差。根据机组故障与特性参数之间的相互关系,得到了机组故障诊断规则。诊断结果表明,该故障检测与诊断策略能有效诊断冷水机组冷凝器结垢故障。

关键词:离心式冷水机组,故障检测,故障诊断,冷凝器结垢,故障阈值

Abstract:

Proposes the fault detection and diagnosis (FDD) strategy based on a model method for centrifugal chillers, selects four performance indexes of strong physical meaning to depict the operation status of centrifugal chillers, establishes a prediction model of property parameters with normal operation data, and obtains the residual error by comparing the calculated value with the reference value. Gets the fault diagnostic rules by analyzing the relation between chiller fault and the property parameters. The fault diagnosis results show that the FDD strategy can detect and diagnose the condenser fault effectively.

Keywords:centrifugal chiller, fault detection, fault diagnosis, condenser scaling, fault threshold

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!

    如果你已经注册但还没登录,请赶紧点此登录吧!