复合式地源热泵系统运行分析
Operating data analysis of a hybrid ground-source heat pump system
摘要:
以某办公楼复合式地源热泵空调系统为例,介绍了该系统的设计思路及运行策略,并详细分析了全年运行数据。通过对实际运行能耗的统计分析,得出供冷供暖单位建筑面积年电耗指标为31.93 kW·h/(m2·a),单位建筑面积供能成本为41.68元/(m2·a),具有较好的示范作用。
关键词:办公楼,复合式地源热泵,运行数据,分析,太阳能热泵,地板辐射供冷
Abstract:
Taking an office building equipped with a hybrid ground-source heat pump air conditioning system as an example, describes the design ideas and operation strategies, and analyses the operation data in details. The analysis of actual energy consumption shows that the annual electricity consumption of the building is 31.93 kW·h/(m2·a) and the energy cost is 41.68 Yuan/(m2·a).
Keywords:office building, hybrid ground-source heat pump, operation data, analysis, solar heat pump, floor radiant cooling