严寒沙尘地区通信机房新型自然冷却通风系统研究

Natural cooling ventilation system for communication rooms in severe cold and dusty areas

夏春华[1],孙国林[1],牛晓然[1],张军甫[1],郭利敏[1],李亚星[1],林超楠[2],周晓慧[2],彭建[2],陈春燕[2]
[1]华信邮电咨询设计研究院有限公司,[2]深圳市筑博建筑技术系统研究有限公司

摘要:

提出一种适用于严寒沙尘地区通信机房的新型空气间接冷却系统,对3种风管自然冷却方案的降温能力进行了实测,并与模拟计算结果进行了比较,验证了模拟方法的可靠性。对某实际工程进行了模拟分析,结果显示,应用该系统节能效果显著。

关键词:通信机房,严寒沙尘地区,自然冷却,模拟分析,实验,节能

Abstract:

Presents a new indirect air cooling system applied to communication rooms located in severe cold and dusty areas. Tests the cooling performance of three air duct natural cooling schemes, makes a comparison between experiment results and simulation results, and verifies the simulation method. With a project example, the simulation and analysis results show that the energy-saving effect is significant after applying this system.

Keywords:communication room, severe cold and dust area, natural cooling, simulation and analysis, experiment, energy saving