小区锅炉房冷凝锅炉改造案例分析
Application case analysis of gas-fired condensing boiler in a district boiler room
摘要:
对北京市某小区进行了冷凝锅炉改造方案设计及运行策略制定。对改造后的应用效果进行了测试,结果表明,改造后的节能效果明显,锅炉效率提升23%;采用冷凝锅炉与采用普通锅炉相比,静态投资回收期增加1.86 a。
关键词:冷凝锅炉,改造,节能效果,经济性分析,回收期
Abstract:
Proposes an application design and operation strategy for condensing boilers of a district boiler room in Beijing. Tests the effect of the application after the transformation. The results show that the energy-saving effect of transformation is obvious.The boiler efficiency rises by 23%, and the static payback period of condensing boilers increases by 1.86 years compared with that of common boilers.
Keywords:condensing boiler, transformation, energy saving effect, economic analysis, payback period