富华国际会议及展览中心空调设计
Air conditioning system design for Fuhua International Convention & Exhibition Centre
摘要:
结合高大空间特点,介绍了各展厅空调系统设计,包括气流组织的确定、系统的划分及机房的设置。第一展厅外区采用下送下回方式、 双层百叶风口,内区采用上送下回方式、旋流风口;第二、三展厅均为内区,采用上送下回方式、旋流风口;共享大厅采用侧送下回方式、球型喷口。水系统采用变水量、两管制系统。介绍了通风、自控设计。
Abstract:
According to the architecture characteristics of large spaces, presents the design of the air conditioning systems, including determination of air distribution, division of the system and setting of the machine rooms. The first exhibition hall adopts the bottom supply and bottom return mode and double registers in the outer zone and adopts the upper supply and bottom return mode and swirl diffusers in the inner zone. The second and third exhibition halls are located in inner zone and all adopt the upper supply and bottom return mode and swirl diffusers. The shared hall adopts the sidewall supply and bottom return mode and globe nozzle outlets. The water system is a variable water flow and twopipe system. Presents design of the ventilation and automatic control systems.
Keywords:large space, air distribution, air conditioning zoning