冷水机组综合部分负荷性能系数(IPLV)计算公式的更新
Revision of integrated part-load value (IPLV) formula for a chiller
摘要:
分析了我国IPLV公式修订的必要性,对IPLV的影响因素进行了分析,并对其计算方法进行了改进;明确了IPLV的计算方法和步骤,通过大量数据分析,提出了IPLV计算所需各项权重系数的确定方法并给出了具体数值;基于典型公共建筑模型数据库对IPLV公式进行了计算,得出了适用于当前我国冷水机组性能水平及使用特点的IPLV公式。
关键词:冷水机组,综合部分负荷性能系数(IPLV),IPLV公式,公共建筑,权重系数
Abstract:
Conducts a comprehensive study on integrated part-load value (IPLV) by characterizing the necessity of the modification of the IPLV formula, and improves the calculation method. Additionally, specifies the calculation method of the IPLV formula associated with its procedures, and proposes a method to obtain the weighting coefficients required in the IPLV formula. By performing calculations on the IPLV formula based on the typical public building model database, achieves a revised IPLV formula which is suitable for the current performance level and features of the chiller in China.
Keywords:chiller, integrated part-load value (IPLV), IPLV formula, public building, weighting coefficient