暖通空调>期刊目次>2013年>第1期

复合式土壤源VRF系统夏季节能特性的实验研究

Experiments on energy saving characteristics of hybrid ground-source VRF system in summer

刘海霞[1],张旭[1],杨洁[1],董丽娟[1],李翔[1],钟鸣[2]
[1]同济大学,[2]大金(中国)投资有限公司

摘要:

详细介绍了系统实验台,并利用该实验台对比分析了冷却塔VRF系统和土壤源VRF系统夏季制冷工况的节能性,得到了两者在夏季制冷运行时部分负荷率下机组EER和系统EER的实际变化规律。冷却塔运行工况下系统EER变化范围为1.19~3.63,地埋管运行工况下系统EER变化范围为1.12~5.4,为复合式土壤源VRF系统的研究和运行策略提供了必要的实验依据。

关键词:土壤源VRF系统,冷却塔,实验研究,部分负荷率,EER

Abstract:

Describes the system test bed in detail, and compares the energy efficient characteristics of cooling tower VRF system and ground-source VRF system in summer, and finds the actual variation regularity of unit EER and system EER in conditions of partial load ratio. The system EER value varies from 1.19 to 3.63 in cooling tower conditions, while from 1.12 to 5.4 in ground-source conditions, providing necessary experiment references for research and operation strategy of hybrid ground-source VRF system.

Keywords:ground-source VRF system, cooling tower, experiment research, partial load ratio, energy efficiency ratio

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!

    如果你已经注册但还没登录,请赶紧点此登录吧!