上海市公共卫生中心呼吸道门诊及病区通风空调设计
Design of air conditioning and ventilating systems for the respiratory infection outpatient department and wards of Shanghai Public Health Center
摘要:
呼吸道传染病房采用新风加带高效过滤器的高余压干式风机盘管机组的空调形式,呼吸道门诊、检验科均采用独立设置的直流式全新风空调系统。针对控制呼吸道传染病的要求,采用了房间负压控制、合理的气流分布、高效过滤排风等技术,取得了较好的效果。
关键词:呼吸道传染病,干式风机盘管,高效过滤,负压
Abstract:
The respiratory infection wards adopt the air conditioning system of fresh air plus dry fan coil units with high residual pressure and high efficiency filter, the outpatient department and the clinical laboratory all adopt independent direct allfresh air air conditioning system. To control the respiratory infection, some measures are taken such as ward negative pressure control, reasonable air distribution and high efficiency exhaust air filtration, obtaining better effects.
Keywords:respiratory infection, dry fan coil units, high efficiency filtration, negative pressure