潜热、显热分级处理的复合空调系统性能研究
Performances of a hybrid air conditioning system withseparate processing of latent and sensible heat loads
摘要:
在实验数据的基础上,针对分别采用两种干燥剂(硅胶、氯化锂)的复合空调系统和压缩式空调系统进行了性能比较分析,发现复合空调系统比压缩式空调系统不仅节电25.6%~35.4%,而且由于转轮处理了潜热负荷可使蒸气压缩制冷系统蒸发器面积减少11.1%~156%,冷凝器面积减少15.4%~21.4%。
关键词:潜热负荷,显热负荷,除湿转轮,复合空调系统
Abstract:
Based on the tested data, compares the performances of the hybrid air conditioning systems with the desiccant wheels respectively coated with silica gel and LiCl with those of the compression-type air conditioning system. The results show that the hybrid air conditioning system consumes less electricity energy than the vapor compression air conditioning system by 25.6% to 35.4%, and reduces the area of evaporator by 11.1% to 15.6% and the area of condenser by 15.4% to 21.4% when the desiccant wheels dealing with latent heat load.
Keywords:latent heat load, sensible heat load, desiccant wheel, hybrid air conditioning system