基于间接蒸发冷水机组的串联空调系统设计方法
Design method for series connection air conditioning system based on indirect evaporative chiller
摘要:
基于间接蒸发冷水机组的串联空调系统是推广使用蒸发冷却技术的一种较好形式。介绍了这种串联系统的工作原理,并给出了其设计计算流程。详细探讨了系统水温升计算、送风参数确定、新风量计算、室内负荷分配、水量平衡、设备选型等主要设计步骤。通过一个设计实例,阐述了具体设计过程,验证了设计方法的可行性。指出了设计过程中需要注意的问题。
关键词:蒸发冷却,干式风机盘管,串联,空调系统,设计方法
Abstract:
This system is a better form of promoting the use of evaporative cooling technology. Presents the principle of the series connection air conditioning system and proposes its design and calculation process. Discusses the water temperature rise, supply air parameters determination, fresh air requirement calculation, indoor load distribution, water flow rate matching and equipment selection in detail. With a design example, proposes the specific design method and testifies the feasibility of the design method. Presents problems worthy of note in design.
Keywords:evaporative cooling, dry fan coil, series connection, air conditioning system, design method