南方某地铁站蒸发冷凝冷水机组能效测试分析
Performance test of an evaporative condensation water chiller used in an underground railway station in southern China
摘要:
为检验蒸发冷凝冷水机组的运行性能,对南方某地铁站车站设备管理用房冷源进行了改造,将原有2台风冷机组中的1台替换为相同冷量的蒸发冷凝冷水机组。在相同负荷、相同环境条件下对两种机组的性能和能耗进行了测试分析,发现蒸发冷凝冷水机组运行效果较优,可以达到预期的节能运行目标。
Abstract:
In order to examine the performance of evaporative condensation water chillers, reforms the cold source of equipment management room of an underground railway station in a city of southern China. Replaces one of the two air-cooled chillers with an evaporative condensation water chiller, which has the same cooling capacity as that of the original air-cooled one. Tests the energy consumption and performances of these two kinds of chillers under the condition of the same indoor cooling load and the same outdoor temperature and humidity. The result shows that the performance of the evaporative one is higher than that of the air-cooled one, which can achieve the expected performance.
Keywords:underground railway station, evaporative condensation water chiller, air-cooled chiller, performance, test