地下商场空调设计问题探讨
Some issues in air conditioning design for underground stores
摘要:
指出客流密度取值偏小和遗漏再热负荷是某些地下商场空调设计负荷偏小的原因,给出了提高换气次数、选用调温除湿型空调机组并辅以合理的运行管理及调节方式的解决办法。
关键词:地下商场,客流密度,再热负荷,换气次数,调温除湿机
Abstract:
Maintains that underestimated customer flow and omission of reheat load cause the air conditioning design load lower than required for some underground stores. Provides a solution by increasing air changes, using temperature-regulation dehumidifiers and adopting appropriate operating modes.
Keywords:underground store, customer flow, reheat load, air changes, temperature-regulation dehumidifier