暖通空调>期刊目次>2008年>第10期

闭式冷却塔的热力特性分析及数值求解

Thermodynamic characteristics and numerical calculation of closed cooling tower

刘乃玲[1], 邵东岳[2],陈兆涛[3]
[1]山东建筑大学,[2]济南同圆建筑设计研究院,[3]山东建筑大学

摘要:

建立了顺流式、逆流式闭式冷却塔热质交换的数学模型,采用四阶Runge-Kutta方法进行了数值计算,并将计算结果与实验值进行了对比。模拟并分析了两种不同运行方式下闭式冷却塔内冷却水温度、喷淋水温度以及空气比焓的分布。

关键词:闭式冷却塔,数学模型,顺流,逆流,数值计算

Abstract:

Sets up a heat and mass transfer mathematical model for both parallel and counter flow type closed cooling towers. Calculates the model by fourth order Runge-Kutta numerical method and compares the results with those from experiment. Simulates and analyses the distributions of cooling water temperature, spray water temperature and air enthalpy.

Keywords:closed cooling tower, mathematical model, parallel flow, counter flow, numerical calculation
本站下载
镜像服务器下载