暖通空调>期刊目次>2014年>第7期

分体空调房间夏季室温波动度的实测分析

Field measurement and analysis on temperature fluctuation range of room with split air conditioners in summer

李兆坚[1,2],张清[2],吕伟[3],邢科伟[1,2]
[1]航天低温推进剂技术国家重点实验室,[2]总装备部工程设计研究总院,[3]中煤科工集团武汉设计研究院

摘要:

为了解分体空调房间夏季室温波动度的实际状况,于20112014年夏季,在北京、武汉和海南三地,对分体空调房间的室温波动度进行了大量实测,并与一些集中空调房间室温波动度测试数据进行对比。结果表明,即使是采用定速分体空调器的房间,其空调恒温阶段的室温波动幅度并不大,为12 ℃,温度控制精度为±0.5  ±℃,小于一些恒温恒湿集中空调房间的空调室温波动幅度。

关键词:分体空调,房间,夏季,室温波动度,实测

Abstract:

In order to understand the actual situation of temperature fluctuation range of room with split air conditioners in summer, field measurement is done in Beijing, Wuhan and Hainan in the summers from the year 2011 to 2014. Compares the temperature fluctuation range with that in some central air conditioning rooms. The results show that even in the room with a constant speed air conditioner, the air temperature fluctuation is 1 to 2 during the air conditioning temperature control stage and the temperature control precision is ±0.5 to ±1 , less than those of some of the central air conditioning rooms.

Keywords:split air conditioner, room, summer, temperature fluctuation range, field measurement