暖通空调>期刊目次>2008年>第8期

过冷式数码多联蓄能机组的实验研究

Experimental research on commercial digital VRF multi-connected units with sub-cooled ice storage system

肖洪海,黄玉优,樊华云,沈军
珠海格力电器股份有限公司制冷技术研究院

摘要:

根据大过冷度制冷循环原理,开发了新型商用数码多联机组并在样机上进行了实验研究。新机组能够在蓄冰、释冷、常规制冷、蓄热、释热与常规热泵6种模式下运行;低谷蓄冰模式运行时间约8 h,能够蓄存378 MJ冷量,铜管外结冰厚度为35 mm;能够保证系统融冰供冷8 h,冷量增加约30%左右;能够运行蓄热与释热模式,在释热模式下,由于蒸发温度提高,可以有效缓解结霜现象。

关键词:过冷,制冷循环,蓄能机组,多联机组

Abstract:

According to the high sub-cooled refrigeration cycle theory, develops a commercial digital multiple variable refrigerant flow rate air conditioning system and carries experimental research on a model machine which proves to be operating under the following six modes: ice charging, ice discharging, normal refrigerating, heat charging, heat discharging and heat pump operation. The period of the ice charging operation is about 8 hours, 378 MJ of cool storage capacity is achieved and the ice thickness of out surface of the copper tube is 35 mm; the cool capacity increases by about 30 percent, the endurance of ice discharging is about 8 hours;and the novel system can operate in the heat charging mode and heat discharging mode, the latter mode allows alleviating the frost formation because of the rise of the evaporating temperature.

Keywords:sub-cooled,refrigerationcycle,energystorageunit,multi-connectedunit

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!

    如果你已经注册但还没登录,请赶紧点此登录吧!