暖通空调>期刊目次>2008年>第7期

地铁集中供冷系统二次泵管路经济流速和经济保温厚度的确定

Determination of economic velocity and economic insulating layer thickness of secondary pump system for central cooling system of underground railway stations

彭金龙,吴炜
中铁二院工程集团有限责任公司

摘要:

结合工程实例,通过建立二次泵变流量系统的优化模型,以年成本最低为原则,对地铁系统二次泵管路经济流速和经济保温厚度进行了计算和分析,得出影响经济流速的主要因素是管材类型、电价、区间隧道温度、输送半径、车站负荷、保温层价格及其导热系数,影响保温厚度的主要因素是区间隧道温度、电价、保温层价格及其导热系数、系统COP、车站负荷和冷水供水温度。采用大温差二次泵变流量系统供水管路和回水管路的热损耗有明显差异,建议结合管路特性,按不同区间分别计算供、回水管路的经济流速和经济保温厚度。

关键词:二次泵变流量系统,优化模型,经济流速,经济保温厚度,最低年成本

Abstract:

With an actual project, develops an optimal model of the variable secondary pump water system, calculates the economic velocity and economic insulating layer thickness with the minimum annual cost as the principle, and obtains that the major influencing factors on economic velocity are pipe type, power price, temperature in section tunnels, transportation radius, cold load of underground railway stations, price and thermal conductivity of insulation materials while the factors on economic insulating layer thickness are temperature in section tunnels, power price, price and thermal conductivity of insulation materials, system COP, cooling load of underground railway stations, temperature of chilled water supply. The analysis result shows that there is a remarkable distinction of heat loss between water supply and return pipelines in large temperature difference variable secondary pump water systems. Therefore, the economic velocity and economic insulating layer thickness should be calculated respectively in term of characteristics of water supply and return pipelines in different section tunnels.

Keywords:variablesecondarypumpwatersystem,optimalmodel,economicvelocity,economicinsulatinglayerthickness,minimumannualcost

    你还没注册?或者没有登录?这篇期刊要求至少是本站的注册会员才能阅读!

    如果你还没注册,请赶紧点此注册吧!

    如果你已经注册但还没登录,请赶紧点此登录吧!