一个特殊的奥运场馆——射击馆的资格赛馆暖通空调设计
HVAC design of a special Olympic Games hall—the shooting qualification competition hall
摘要:
介绍了射击资格赛馆的特殊性以及针对其特殊性所作的设计。针对1层两个比赛厅北墙敞开的特点,采用全空气空调系统、排风从敞开空间自然排出方案;针对空调机房距4个比赛厅仅一墙或一板之隔的特点,空调机隔振采用浮筑楼板加减振台板、隔声采用双墙中间夹隔声材料层的方案;针对奥运会后观众区改作他用、运动区继续作集训使用的特点,观众区和运动区各有一套空调系统,运动区另设风机盘管和地板供暖;针对步枪、手枪射击时产生弹药味的特点,采用吊顶设通风格栅、高窗设电动开启的自然通风方案。
Abstract:
Presents the particularity of the qualification competition hall and its design. Adopts the all-air and natural ventilation system for the opening north wall; the floating floor and isolation table to isolate machine vibration, the sounds insulation materials between two walls to insulate noises in the plant; the air conditioning system separately for the audience area and sports area, the fan-coil unit and floor heating system only for the sports area to adapt the use after the Olympic Games; the natural ventilation modes of air grid at ceiling and electric opening in the upper position of the walls to eliminate the ammunition odor.
Keywords:shooting qualification competition hall, all-air system, vibration isolation, natural ventilation