分户热计量垂直供暖系统的水力计算
Hydraulic calculation for vertical heating systems for household heat metering
摘要:
通过实例,对分户热计量下供下回双管系统进行了水力计算。结果表明,将本层较下层增加的自然循环压力消耗于层间的公共立管上可以避免双管供暖系统中的垂直失调。
关键词:供暖系统,分户热计量,水力计算
Abstract:
With an example, presents the hydraulic calculation for two-pipe upfeed system for household heat metering. The results show that the vertical imbalance of two-pipe heating system can be avoided by consuming the natural circulation power higher than the adjacent under floor on the public riser as much as possible.
Keywords:heating system, household heat metering, hydraulic calculation