复合型太阳能溶液除湿空调的性能模拟
Performance simulation of compound solar liquid desiccant air conditioning
摘要:
结合热湿地区的气候特点,设计了复合型太阳能溶液除湿空调系统,并通过数值模拟,分析了除湿器和再生器入口空气参数对系统性能的影响。结果表明,除湿器入口空气温、湿度从36 ℃和80%冷却减湿预处理到26 ℃和90%时,除湿器的体积可减小约63%,溶液循环量减小约58%;使用房间排风作为再生空气源,可明显提高溶液的再生效率和浓度,有效降低再生热源温度。
Abstract:
In accord with the climatic conditions in hot-humid areas, designs a compound solar liquid desiccant air conditioning system. By establishing a mathematical model, analyses the effects of inlet air parameters of dehumidifier and regenerator on system performance. The results indicate that when dehumidifier inlet air is pretreated from 36 ℃and 80%to 26 ℃ and 90% by cooling and dehumidifying preprocess, the dehumidifier’s volume can be reduced by about 63%, and solution circulating amount about 58%, and that by taking indoor exhaust air as regeneration air, the regeneration efficiency and concentration of liquid can be improved, and the temperature of the regeneration heat source reduced effectively.
Keywords:compound solar liquid desiccant air conditioning, hot-humid area, performance, dehumidifier, regenerator, air parameter