济南奥林匹克体育中心水蓄冷系统设计
Chilled water storage system design for Jinan Olympic Sports Center
摘要:
介绍了工程概况,分析了负荷特点。设计选用的大温差水蓄冷系统采用2台制冷机串联的方式实现大温差制冷,供回水温度为3.5 ℃/12.5 ℃,蓄冷水罐有效容量为9 000 m3,蓄冷量为89 250 kW·h。
关键词:济南奥林匹克体育中心,水蓄冷,区域供冷,设计
Abstract:
Presents the general situation of the project and analyses its load characteristics. The large temperature difference chilled water storage system designed adopts two series-arranged refrigerating machines to accomplish large temperature difference cooling, the supply water temperature is 3.5 ℃, and the return water temperature is 12.5 ℃, the effective capacity of chilled water storage tank is about 9 000 m3, and the cool storage capacity is 89 250 kW·h.
Keywords:Jinan Olympic Sports Center, chilled water storage, district cooling,design