西直门综合交通枢纽工程空调通风系统设计
Air conditioning and ventilation system design for the Xizhimen Exchange Hub Project
摘要:
介绍了西直门综合交通枢纽工程空调通风系统的优化设计。采用了多项空调节能措施:大冷量离心冷水机组搭配变频小冷量机组,二次泵变频变流量空调水系统,四管制风机盘管冬季用冷却塔换冷供冷设计,商业外区风机盘管、内区全空气空调系统,送风机、排风机变频控制,过渡季、冬季利用室外新风通风降温的焓值控制设计。
关键词:大型公共建筑 集中空调系统 通风 系统设计 节能
Abstract:
Presents the optimized air conditioning and ventilation system design. Takes several energy saving measures for air conditioning system, such as large capacity centrifugal chillers working with variable frequency small capacity chillers, variable frequency and variable flow control on secondary pump water systems, cooling tower for fourpipe water system in winter, fancoil unit for commercial peripheral zones and allair systems for interior zones, variable frequency control on supply and exhaust air fans, enthalpy control on fresh air cooling in winter and intermediate season.
Keywords:largescale public building, central air conditioning system, ventilation, system design, energy saving