蒸发冷却空调应用的气候适应性区域划分
Climate demarcating for application of evaporative cooling air conditioning
摘要:
采用湿球温度作为区域划分指标,以夏季空调室外计算湿球温度为20,23,28 ℃作为分区指标的临界值,将基本覆盖全国范围的177个城市划分为通风区、高适应区、适应区及非适应区四个区域。
关键词:蒸发冷却,气候适应性,湿球温度,区域划分
Abstract:
Taking the wet-bulb temperature as district index and the outdoor design wetbulb temperature for summer air conditioning of 20, 23, 28 ℃ as the critical values, divides 177 cities nationwide into four application regions, including ventilation region, high adaptability region, adaptability region and non-adaptability region.
Keywords:evaporative cooling, climate adaptability, wet-bulb temperature, region division