游泳馆空调负荷计算探讨
Discussion on calculation of air conditioning load for natatoria
摘要:
通过对游泳馆内池水蒸发换热及池水与室内空气之间的显热换热分析,推导出池水蒸发潜热负荷计算公式。结合工程实例,计算了池水蒸发潜热量,得出池水蒸发潜热负荷是空调负荷的一个重要影响因素。
关键词:换热分析,池水,蒸发,潜热负荷
Abstract:
Based on the analysis of pool water evaporation heat transfer and the sensible heat transfer between indoor air and pool water, deduces the calculation formula of latent load by pool water evaporation. With a project example, calculates the latent heat by pool water evaporation, and concludes that the pool water evaporation is an important factor influencing air conditioning load.
Keywords:heat transfer analysis, pool water, evaporation, latent heat load