平面液膜蒸发式冷凝空调系统的工程应用
Application of plane liquid film plate-type evaporative condensing air conditioning system to a project
摘要:
介绍了该空调系统在广东某学术交流中心的应用,并与水冷式和风冷式空调系统在节能性、经济性、环保性等方面进行了对比。结果表明,平面液膜蒸发式冷凝空调系统的性能系数比风冷式提高30.5%,比水冷式提高12.7%;运行费用比风冷式降低31.0%,比水冷式降低16.5%;其相对于水冷式空调系统的节水率为54.5%。
Abstract:
Presents the application of this system to an academic communication centre in Guangdong Province, and compares the system to water-cooling and air-cooling air conditioning systems in terms of energy saving, economical efficiency and environmental protection. The results show that the coefficient of performance (COP) of the evaporative condensing system is 30.5 percent higher than that of the air-cooling system and 12.7 percent higher than the water-cooling system; the operating cost of the system is 31.0 percent lower than that of the air-cooling system and 16.5 percent lower than the water-cooling system; and that the ratio of water saving of the system is 54.5 percent compared to the water-cooling system.
Keywords:plane liquid film evaporative condenser, water-cooling, air-cooling, energy saving, air conditioning system