中国电信通信指挥楼/北京电信通信机房楼空调系统设计
Design of air conditioning system for China/Beijing Telecom Building
摘要:
介绍了该工程的空调系统设计。工艺性空调房间主要采用了风冷式机房专用空调机组,舒适性空调房间采用风机盘管加新风系统。系统分内、外区,水系统为两管式。设计解决了多种功能房间对空调系统的需求问题,满足了电信工艺机房对空调系统负荷容量及不间断运行方面的要求,同时考虑了工艺用房在气体消防后的事故通风问题。
Abstract:
Presents the HVAC system design. The process air conditioned rooms adopt equipment room dedicated air cooled air conditioning units, and the comfort air conditioned rooms adopt fan-coil unit plus fresh air system. Conditioned area with two-pipe water system is divided into inner zone and peripheral zone. Represents solutions to air conditioning system demand of rooms with different functions at the same time, and to the request for cooling capacity and continual operation in air conditioning system of the telecom industrial room, and takes into account the emergency ventilation after gas extinction.
Keywords:telecom plant, air conditioning system, design