暖通空调>期刊目次>2012年>第10期

中国金融信息大厦溶液调湿空调系统节能分析

Energy efficiency analysis of the liquid desiccant air conditioning system in China Financial Information Building

夏勇,孟海
上海陆道工程设计管理有限公司

摘要:

介绍了工程概况和负荷计算,分析了溶液调湿空调系统的节能效果。结果表明,在100%,75%,50%,25%负荷下,溶液调湿空调系统比常规空调系统分别节能13.06%,14.1%,16.96%,24.1%,综合节能率为16.4%。

关键词:工程概况,负荷计算,溶液调湿,系统能耗,节能效果

Abstract:

Presents the general situation and load calculation of the project and analyses the energy saving effects of the system. The results show that the liquid desiccant air conditioning system can save energy by 13.06%,14.1%,16.96%,24.1% separately under 100%, 75%,50%,25% of the full load than that of a conventional air conditioning system, and the comprehensive energy saving rate is 16.4%.

Keywords:general situation of project, load calculation, liquid desiccant,system energy consumption, energy saving effect