暖通空调>期刊目次>2014年>第11期

严寒地区岩土热响应试验与地埋管地源热泵系统应用

Rock-soil thermal response test and application of ground-source heat pump in severe cold zone

葛凤华[1],刘红楷[1],王剑[1],段舒娅[1],周英利[2]
[1]江苏大学,[2]中元国际(长春)高新建筑设计院有限公司

摘要:

结合严寒地区某工程,建立了两口120 m深U形竖直埋管试验井并进行热响应试验,利用Kelvin无限长线热源理论模型计算了岩土层热物性参数及地埋管换热器的换热能力,分析了地埋管换热器的热阻特性,得出了夏季直接取冷条件下的单井取冷量与冷水温度的关系,并给出空调方案。依据土壤热平衡、初始土壤温度、地埋管换热器的换热能力及全年负荷等因素,确定了太阳能结合土壤蓄热的地埋管地源热泵系统供热供冷方案。

关键词:太阳能-地埋管地源热泵,热响应试验,地埋管换热器,温度湿度独立控制,严寒地区

Abstract:

Combining with a ground-source heat pump project in severe cold zone, builds two vertical U-tube test wells with depth of 120 m to conduct thermal response test. By using Kelvin’s infinite linear source model, calculates parameters of rock-soil thermal properties and capability of ground heat exchanger (GHE). Analyses the thermal resistance characteristics for GHE. Obtains the relationship between extracting cooling capability per well and cooling water temperature under the direct heat exchange condition in summer. Puts forward air conditioning scheme. According to ground heat balance, initial rock-soil temperature, capability of GHE and the year loads, determines the heating and cooling supply schemes of solar coupled ground-source heat pump system.

Keywords:solar coupled ground-source heat pump system, thermal response test, ground heat exchanger, temperature and humidity independent control, severe cold zone