暖通空调>期刊目次>2006年>第8期

地铁区间隧道火灾通风模式的数值分析

Numerical studies on ventilation modes in underground railway tunnel fire

周孝清,赵相相,丁云飞,郑志敏
广州大学

摘要:

介绍了地铁区间隧道火灾常见的几种通风排烟模式,对其中一种最复杂的模式进行了数值分析。模拟分析得出,对于地铁实际工程中的单线盾构圆形隧道,在10 MW火灾强度下,着火区间隧道内2.6~2.9 m/s左右的纵向风速可以有效阻止烟气发生逆流;在着火区间隧道2.9 m/s的纵向风速下,未着火区间隧道两端对送送风速度为1~1.5 m/s时,联络通道内有风速为6 m/s左右的气流流向着火区间隧道,可有效抑制烟气通过联络通道向未着火区间隧道蔓延,保证人员的安全疏散。

关键词:地铁区间隧道火灾 通风排烟模式 临界风速 联络通道

Abstract:

Presents several ordinary ventilation and smoke extraction modes,and simulates the most complex one of them. The results show that for the single-track shield tunnel in actual projects,the longitudinal ventilation velocity of 2.6~2.9 m/s can effectively prevent smoke from counter flow at a heat release rate of 10 MW; when the tunnel sector on fire with a longitudinal velocity of 2.9 m/s and the unfired tunnel sector with the velocity of 1~1.5 m/s from both ends,there is an air flow with the velocity of 6 m/s to the tunnel on fire in the connected tunnel,so the smoke diffusion to the unfired tunnel is effectively prevented,and the security of evacuation is ensured.

Keywords:underground railway tunnel fire,ventilation and smoke extraction mode,critical velocity,connected tunnel
本站下载
镜像服务器下载