空调百叶风口防风雨性能的测试分析

Testing and analysis on the weatherproof performance of air conditioning register

李兆坚[1,2],舒安源[2]
[1]航天低温推进剂技术国家重点实验室,[2]航天低温推进剂技术国家重点实验室

摘要:

为了解空调百叶风口在台风暴雨气象条件下的防风雨性能,对普通型和防雨型百叶风口的防风雨性能进行了实测研究。结果表明:普通单层固定百叶风口只能抵御不超过4级风造成的风雨袭击,防雨百叶风口具有较好的防雨性能,但也难以抵御7级以上风造成的风雨袭击,因此设置防雨百叶风口并不是抵御台风暴雨侵袭的一种有效措施。

关键词:航天低温推进剂技术国家重点实验室,总装备部工程设计研究总院,轩志勇,徐元元

Abstract:

In order to understand the weatherproof performance of the air conditioning register in typhoon rainstorm weather conditions, tests and analyses the weatherproof performance for a common type register and a rainproof register. The results show that the single fixed register cannot resist the attack of rainstorm under the wind over four-level. The rainproof register has better weatherproof performance, but it is difficult to resist the rainstorm attack under the wind over seven-level, so setting rainproof register is not an effective measure against the invasion of the typhoon rainstorm.

Keywords:air conditioning register, weatherproof, performance, test, typhoon