暖通空调>期刊目次>2006年>第10期

利用城市污水热能供热的实验研究

Experimental research on recovery and utilization of urban sewage heat energy

白莉[1],尹军[1],张喜明[2]
[1]哈尔滨工业大学,[2]吉林建筑工程学院

摘要:

研制了以水源热泵为中心设备的污水热能回收利用实验系统,获得了用铝塑复合管间接回收污水热能的技术方法,解决了污水热能利用的关键性问题,即换热设备的腐蚀问题。研究结果表明,污水热能回收利用实验系统能满足冬季供热负荷的要求,系统平均供热系数可达32。

关键词:城市污水,热能利用,实验研究,水源热泵

Abstract:

Develops the recovery and utilization experimental system of sewage heat energy based on water-source heat pumps. Obtains the technique of indirect heat exchange by PAP to reclaim sewage heat energy and resolves the key problem of the utilization of urban sewage heat energy, i.e., corrosion of heat exchangers. The experimental results show that the system can satisfy the demand of heating in winter with the average COP of the system up to 32.

Keywords:urban sewage, heat energy utilization, experimental research, water-source heat pump